More Details

Product overview
  • Built-in check valve — prevents air re-entry when system pressure drops below atmospheric pressure
  • Top-mounted replaceable seat and check valve assembly — positioned above the shell, isolated from suspended dirt; removable for quick cleaning or replacement
  • Dual inlet connections: 1/2 in. female NPT and 3/4 in. male NPT — installation flexibility for a range of piping configurations
  • 1/8 in. NPT air outlet — accepts piped drain connection where any water discharge is unacceptable
  • Maximum operating pressure: 75 psig; maximum hydrostatic pressure: 200 psig
  • Maximum operating temperature: 250°F (121°C)
  • Vents up to 850 SCIM — only vent in this category with published capacity ratings
  • Brass body; brass or stainless steel float — suitable for water and glycol systems
  • Install at all high points in the system and on all air separating devices; use minimum 3/4 in. pipe with ball-type shutoff for serviceability without system drain-down
  • Professional installation required
Specifications
Manufacturer Part Number 401488
UPC 751875018507
Overall Dimensions n/a
Material n/a
Domestic or Import n/a
End Style n/a
Type Water Main
ADA Compliance n/a
Warning Professional installation required
Standards and Approvals n/a